home > mps1076-000
MPS1076-000 300Watt Built-in UPS
(PS/2 Case, ATX-Style Connector,Contact-
Closure-Compatible Control Interface.)
MPS1076-000 is a plug-in replacement for conventional NLX/ATX form-factor
switching power supplies. Units function as a normal power supply
when AC line input is present and as truly on-line UPS during periods of
power failure. Suitable for operation in conjunction with Magnum 24V
battery packs.
Features:
300W Continuous DC Output Power* . Active PFC . Full UPS functionality . Wide-ranging AC
Input (47Hz to 63Hz, 90V to 260V) . Five DC Outputs . High power Standby Output (+5Vsb /2.5A) . Hold-up
Time >16ms (No Battery Fitted) . Efficiency >65% (AC/DC & DC/DC) . Overtemperature, Overvoltage &
Overcurrent Protection (Latched Shutdown) . Fan Speed Control . Standard UPS Contact Closure
Compatible Interface . Logic On/Off . PS/2 (NLX) Style Case . ATX (NLX) 20-Way Motherboard Connector
* Output power derated by -5W/°C above 25°C
1. Output (standard)
| Nominal Voltage |
Min Load |
Max Load |
Regulation |
Ripple &
Noise |
| +5V DC |
0.3A |
28A (1) |
+/-5% |
50mV |
| +3.3V DC |
0.5A |
28A (1) |
+/-5% |
50mV |
| +12V1 DC |
0.5A |
12A (2) |
+/-5% (2) |
120mV |
| +12V2 DC |
0.5A |
11A (2) |
+/-5% |
100mV |
| -12V DC |
0A |
0.8A |
+/-5% |
120mV |
| +5Vsb |
0A |
2.5A |
+/-5% |
100mV |
(1) The combined loading on the +5V DC and the +3.3V DC outputs must not exceed 220W.
(2) 12V surge of 15A allowed for 15 seconds.
2. Overcurrent
| +5V, +3.3V, +12V1 , +12V2 |
Latched shutdown at <240VA (SELV Limit)
AC line or Logic On/Off recycle to restart. |
| -12V |
Short circuit protected. Latched shutdown.
AC line or Logic On/Off recycle to restart. |
| +5Vsb |
Short Circuit protected. Automatic recovery |
3. Overvoltage
| +5V, +3.3V, +12V1 , +12V2, -12V |
Latched shutdown at 5.6V to 6.6V, 3.7V to 4.5V, 13.2V to
15.6V, -15.6V to -13.2V, respectively.
AC line or Logic On/Off Recycle to start. |
| +5Vsb |
Clamped at 5.9V to 6.5V. Automatic recovery |
4. Backup Battery
| Battery Type |
24V Lead acid |
| Charger Voltage |
27.6V (Temperature compensated) |
| Charger current limit |
1.0A (Max) |
5. Approvals
| Safety |
Designed to comply with EN60950 |
| EMC (Emissions) |
EN55022 Class B, CISPR 22 Class B, FCC CFR 47 Part 15
Class B |
| EMC (Immunity) |
EN61000-4-2, EN61000-4-4, EN61000-4-5 |
| EMC (Harmonic) |
EN61000-3-2 |
| Other |
CE Mark |
7. Control Interface
| PSON (LOGIC ON/OFF) |
BI-UPS® Input. TTL compatible siganl setting on/off state of unit.DC outputs enabled if pulled to logic low. DC outputs (excluding +5Vsb) disabled if driven to logic high or open circuited. |
| Power Good |
BI-UPS® Output. TTL compatible flag indicating status of +5V and +3.3V outputs. Set to logic high between 100ms and 500ms after both +5V and +3.3V outputs reach normal operating limits. Reset to logic low at least 1ms prior to either +5V or +3.3V outputs dropping out of normal operating limits. |
| Interface Enable |
BI-UPS® Input. Discrete signal to enable BI-UPS® control interface. Interface inactive if open circuited or held at logic low (-5 to -15V). Interface enabled if driven to logic high (+5 to +15V). |
| AC Fail |
BI-UPS® Output . RS232 compatible flag indicating failure of ac line voltage. ‘AC normal’ condition indicated by logic high (+5 to +15V); ‘AC fail’ by logic low (-5 to -15V) |
| Battery Backup Low |
BI-UPS® Output. RS232 compatible flag indicating battery backup voltage low. ‘Battery normal’ condition indicated by logic high (+5 to +15V); ‘Battery Low’ by logic low (-5 to -15V). |
| Shutdown |
BI-UPS® Input.Discrete signal enabled during battery back-up operation only. No action taken if held at logic low(<1V) or Open circuited. BI-UPS® shutdown initiated if driven to logic high (+5V to +15V). |
8. Environmental
| Storage Temperature |
-40 to +85° |
| Operating Temperature |
0 to 50°C (output power derated -5W/°C above 25°C) |
| Humidity |
5 to 95% (non-condensing) |
| Maximum Altitude |
12,000ft (operating), 40,000ft (non-operating) |
| Shock |
15g pk for 11ms (operating), 30g pk for 11ms (nonoperating) |
| Vibration |
0.006 inch pk-pk @ 10 to 57Hz, 1.0g @ 57 to 150Hz
(operating) |
| MTBF |
>80,000 hours calculated per MIL-HBK-217F (full-load, 35°C, ground benign, ex fan) |
9. Cable Harness
| Designator |
PIN |
COLOUR |
FUNCTION |
P1
Molex 39-01-2200 |
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20 |
Orange
Orange
Black
Red
Black
Red
Black
Grey
Violet
Yellow
Orange
Blue
Black
Green
Black
Black
Black
N/C
Red
Red |
+3.3VDC
+3.3VDC
DC Return
+5VDC
DC Return
+5VDC
DC Return
Power Good
+5Vsb
+12V1DC
+3.3VDC
-12VDC
DC Return
PSON
DC Return
DC Return
DC Return
N/C
+5VDC
+5VDC |
P2, 4
Molex 8981-04P |
1
2
3
4 |
Yellow
Black
Black
Red |
+12V2DC
DC Return
DC Return
+5VDC |
P3, 5
Molex 8981-04P |
1
2
3
4 |
Yellow
Black
Black
Red |
+12VDC
DC Return
DC Return
+5VDC |
P6, 7
Amp 171822-4 |
1
2
3
4 |
Yellow
Black
Black
Red |
+12V2DC
DC Return
DC Return
+5VDC |
P8, 9
Amp 171822-4 |
1
2
3
4 |
Red
Black
Black
Yellow |
+5VDC
DC Return
DC Return
+12VDC |
P10
Molex 90331-0010 |
1
2
3
4
5
6 |
Black
Black
Black
Orange
Orange
Red |
DC Return
DC Return
DC Return
+3.3VDC
+3.3VDC
+5VDC |
P11
Molex 39-01-2040 |
1
2
3
4 |
Black
Black
Yellow
Yellow |
DC Return
DC Return
+12VDC
+12VDC |
P12
Alex 6420-02M1 |
1
2 |
Red
Black |
Battery +VE
Battery –VE |
P13, P14
Molex 88751 |
1
2
3
4
5 |
Yellow
Black
Red
Black
Orange |
+12V2DC
DC Return
+5VDC
DC Return
+3.3VDC |
P15
Molex 39-01-2040 |
1
2
3
4 |
Black
Black
Yellow
Yellow |
DC Return
DC Return
+12V1DC
+12V1DC |
P16 9-Way D-type
female)
Leoco
DB095RRR30CDDD1 |
1
2
3
4
5
6
7
8
9 |
Orange
N/C
Brown
Red
N/C
N/C
Yellow
Green
N/C |
Battery Low
N/C
Ground
Shutdown
N/C
N/C
Ground
AC Fail
N/C |
10. Mechanical - Standard Chassis
|